DC Fuse & Breaker Size Calculator

General guidance

A widely used rule (from NEC-style continuous-load practice) sizes overcurrent protection at 125% of continuous current, rounded up to the next standard size, while never exceeding the ampacity of the wire it protects. Put the fuse as close to the battery positive as practical. Lithium banks can deliver very high short-circuit current, so many manufacturers specify a Class-T fuse at the battery. Solar strings use the panel maker's maximum series fuse rating. Your equipment manual overrides any rule of thumb.

Continuous AFuse
1015
2025
3040
4050
6080
80100
100125
150200
200250

Safety: These are general estimates, not a design. Follow your equipment manufacturer's instructions and local electrical code, and consult a qualified electrician for anything connected to shore power, a house, or high-current batteries.

FAQ

What size fuse for a 2000W inverter?

At 12 V a 2,000 W inverter can draw about 185 A continuous; 125% is about 231 A, so the next standard size is 250 A, with wire rated for it (often 2/0–4/0). Follow the inverter manual's specified fuse.

Fuse or breaker?

Both work if they are DC-rated for your voltage and interrupt current. Breakers can double as disconnects.